Cause & Effect / Logic
PROGRAMMING KNOWLEDGE

Cause & Effect / Logic

A practical guide to fire-alarm logic, staged operation, coincidence, delays, inhibits, network scope and commissioning proof.

Before changing a live system: agree the test/disablement with the responsible person, identify any ARC/fire-routing connection and plant interfaces, decide what must remain operational, record every temporary change, and restore/verify everything before leaving.
OR

Any cause

Any selected input can drive the effect. Typical example: any detector or MCP in a fire zone starts local warning.

AND

Confirmed / double knock

Two independent conditions must be true before the effect operates. Use only where the design/fire strategy requires confirmed operation.

DELAY

Timed action

An effect operates after an investigation or staged-alarm delay. Confirm how MCPs, evacuation and manual controls override the delay.

INHIBIT

Conditional suppression

A keyswitch, time clock, test mode or other condition prevents an effect. Make the inhibited state visible and easy to restore.

CAUSE & EFFECT WORKFLOW

Commission logic from the fire strategy, not from memory

  1. Define causes: device, zone, group, sprinkler, suppression, BMS or other input.
  2. Define effects: sounders/VADs, routing, doors, lifts, fans, dampers, smoke control, suppression interfaces and shutdowns.
  3. Define logic: OR, AND, coincidence, delays, time clocks, dependencies, overrides and reset behaviour.
  4. Define scope: local panel, sector, network node, building area or system-wide.
  5. Test every path: prove the expected effect and also prove that unwanted effects do not occur.
  6. Document: retain an approved cause-and-effect matrix and note software/configuration revision.
MANUFACTURER TERMINOLOGY

Common names for similar concepts

ManufacturerCommon terminologyEngineer note
AdvancedStandard mapping, flexible logic, time clocks, sectors, disablement groupsPC configuration tools provide detailed network-wide cause/effect.
KentecCause & effect, actions, test mode, Loop ExplorerLogical operators can combine zones/inputs to drive outputs.
C-TECInput Groups, Output Groups, Action SequencesZTOOLS is central to ZFP configuration.
GentSectors, groups, command buildsSite-specific Gent configuration terminology is important.
NotifierControl matrix / logic / virtual points depending familyPearl, ID3000 and INSPIRE differ; follow family documentation.
ProtecOutput groups, panel logicSome output groups may be logic/keyswitch controlled rather than manually available.
Eaton xDetectMatrix cause & effect, groups, type IDsxDetectWorks is the configuration environment for trained engineers.
NittanCause & effect matrix / groupsEvolution 1 supports on-panel or PC-tool configuration.
Return to service:Exit test modeClear temporary disablementsRestore sounders / outputsRestore fire routing / ARCRestore delays / time controlsProve a normal event pathCheck panel = normalRecord work