MANUFACTURER KNOWLEDGEBASE

Kentec Engineer Guide

Syncro AS / Taktis: practical field notes for testing, disablements, logic and restoration. Menu wording can vary by firmware and site configuration.

Before changing a live system: agree the test/disablement with the responsible person, identify any ARC/fire-routing connection and plant interfaces, decide what must remain operational, record every temporary change, and restore/verify everything before leaving.
KENTEC

Syncro AS / Taktis

Kentec Syncro-family panels provide clear user-level test-zone and disablement functions, while Loop Explorer is used for deeper cause/effect configuration.

Protocol / ecosystemApollo / Hochiki ESP / Argus Vega depending panel and loop configuration

One-man / walk test

  1. Enter the authorised menu and choose Test Zones.
  2. Select the zone and choose the required sounder behaviour for the test.
  3. Operate devices in the zone; the panel automatically returns from each brief test-fire event.
  4. Use View/Restore Zones in Test or the corresponding menu to remove every test condition.

Disable / enable

  1. Use Disablements to select the required zone, address/sub-address, sounders or panel output.
  2. Remember that a disabled input may still report certain faults depending on panel behaviour.
  3. Use View/Restore Disablements to review and individually clear all active disablements.

Cause & effect / groups

  1. Kentec cause/effect can combine inputs/zones using logical operators to operate outputs across the system/network.
  2. Loop Explorer provides support for actions, test mode and disablement programming.
  3. Treat any cause/effect that disables outputs as a safety-critical function and document its trigger and restoration path.

Engineer notes

  1. Use View Devices for device type, zone, location, analogue value and I/O state during diagnostics.
  2. Confirm the protocol-specific address limit for the installed loop.
  3. Older Syncro manuals and newer Taktis workflows are not identical; verify family and firmware.
Return to service:Exit test modeClear temporary disablementsRestore sounders / outputsRestore fire routing / ARCRestore delays / time controlsProve a normal event pathCheck panel = normalRecord work