Nittan
MANUFACTURER KNOWLEDGEBASE
Nittan Engineer Guide
Evolution 1 / EVO+: practical field notes for testing, disablements, logic and restoration. Menu wording can vary by firmware and site configuration.
Before changing a live system: agree the test/disablement with the responsible person, identify any ARC/fire-routing connection and plant interfaces, decide what must remain operational, record every temporary change, and restore/verify everything before leaving.
NITTAN
Evolution 1 / EVO+
Nittan Evolution panels provide clear zone test modes and full cause/effect capability, with useful official technical guidance sheets for common configuration tasks.
Protocol / ecosystemEvolution FSK
One-man / walk test
- Enter an authorised user/engineer level and open the Zone menu.
- Set the required zone to Test for silent testing, or Test + Sound where the required test includes sounders.
- Operate the device; the panel auto-resets the test fire. On Evolution 1, Test + Sound operates alarm sounders for roughly 10 seconds.
- Return every test zone to normal and accept the change.
Disable / enable
- Use the zone/device disablement functions for maintenance scope.
- Avoid broad zone disablement where a single device can be safely isolated.
- Review all active test/disablement states and clear them before handover.
Cause & effect / groups
- Evolution 1 supports full cause/effect programming on the panel or via PC configuration tools.
- Nittan publishes guidance on default C&E, timed disablement and C&E hints/tips.
- Keep configuration revisions compatible with panel firmware, particularly on networks.
Engineer notes
- Evolution 1 supports up to 254 devices and 254 zones.
- Nittan publishes firmware/network compatibility notes; verify before adding/replacing network panels.
- Use clean-air/contamination guidance when assessing detector condition.
Return to service:Exit test modeClear temporary disablementsRestore sounders / outputsRestore fire routing / ARCRestore delays / time controlsProve a normal event pathCheck panel = normalRecord work
PRIMARY REFERENCES
Manuals and manufacturer resources
External links are references only and require internet access. The knowledgebase itself remains usable offline.